cab2/3ggc2kv
SONECABLE 2 3C GGC 2KV 2AWG 3C GGC 2000V 90CMALT ISOLE
Type G-GC round portable power cable with 8 AWG through 500 MCM fully annealed stranded bare copper conductor. Premium-grade, colour-coded 90°C EPDM insulation. VIPER™ 90°C black jacket. Excellent impact and abrasion resistance. Withstands exposure to oil, acids, alkalies, heat, moisture and most chemicals. Indent-printed for easy identification. Rope lay stranding for maximum flex life. Cable core bound for superior flexibility and toughness. Non-wicking rubber fillers (GGC). Suitable for industrial and light-to medium-duty mining, mobile and portable electrical equipment applications.
Marque | Approved Vendor | Nom de l'item | Câble de masse GGC |
Tension nominale | 2 kV | Dimensions de câble | 2 AWG |
Type de conducteur | Cuivre nu | Nombre de conducteur | 3 |
Brin | 259 | Matériel d'isolation | EPDM |
Matériaux de l'enveloppe | Thermodurcissable CPE | Ampérage nominales | 152 A |
Couleur de l'enveloppe | Noir | Épaisseur de l'isolant | 0,06 pouces |
Diamètre extérieur nominal | 1,345 pouces | Température nominale | 90 ° C |
Normes | Listé UL, certifié CSA, ICEA 5-75-381, approuvé MSHA | Application | Pour utilisation avec tout équipement minier portable, temporaire ou permanent, mobile ou stationnaire, les navettes, les foreuses mobiles, les pompes, les boulons de toit, les convoyeurs et l'alimentation électrique portable lorsque la mise à la terre de l'équipement est nécessaire |
1 - Unité | 304 - Unité | R304 - Unité | 305 - Unité |